Room-temperaturetransducer EGT 130

EGT130F001

The EGT130 room-temperature transducer is used for measuring the temperature for heating and air-conditioning systems in dry rooms such as residential, office and commercial premises. A nickel thin-film sensor as per DIN 43760 is used for measurement. Within the measuring range of the EGT130, the measured values are converted into a linear standard signal of 0...10 V (0.2 V/K). It is also possible to connect an external Ni1000 temperature sensor.

Technical Description

  • Output 0...10V
  • Weight 0.1 kg
  • Measuring range 0...50°C
  • Power supply 24V~/=
  • Operating temperature 0...50°C